tticks I
SAFEGUARDTM
WINDOW MOUNT AIR CONDITIONING
( COOLING ONLY )
FOR HAZARDOUS LOCATIONS


CLASS 1, GROUP BCD, DIVISION 2
All Window Mount Air Conditioners are Rated T3A ( 356deg. F).
Intrinsically Safe Self Contained Controls are standard on each Window Mount Air Conditioner .
Operation:
COOLING ONLY - Off/On switch and temperature control. Blower runs continuously, thermostat setting cycles the compressor
Large condenser fan with slinger
Long lasting washable filter with germicidal treatment
Includes accessories for window * or thru-wall installation
Each Window Mount Air Conditioner has a Closed loop or fresh air and exhaust control
*most models
8 Models of Cooling only Window Mount Air Conditioners are CSA Listed for Hazardous Location Application..
Intrinsically Safe Self Contained Controls
Heavy Duty ultra-quiet operation
Slide-out chassis for easy instillation and maintenance
Totally enclosed split capacitor fan motor
Options:... coatings
Polyurathane enamel corrosion protected hermetic system, includes evaporator coil, condenser coil, compressor, and all connecting tube
Polyurathane enamel coating of entire unit. Custom colors available
Cooling only Models from 8400 BTU to 36000 BTU, 115 Volt to 230/208 Volt
SPECIFICATIONS for Cooling Only Window Mount Air Conditioners
| MODEL | COOLING CAPACITY BTU/HR |
ELECTRICAL CHARACTERISTICS | CIRCUIT RATING | EER | AIR MOVING CAPACITY | ||
| VOLTS | AMPS | WATTS | |||||
| MC2081SC-BCD | 8400 | 115 | 6.6 | 737 | 125V-15A | 11.4 | 265 CFM |
| MC2101SC-BCD | 10,400 | 115 | 7.5 | 867 | 125V-15A | 12.0 | 260 CFM |
| MC2121SC-BCD | 12,000 | 115 | 9.0 | 1000 | 125V-15A | 11.8 | 350 CFM |
| MC2122SC-BCD | 12,000/11,900 | 230/208 | 4.8/5.0 | 1052/1017 | 250-15A | 11.5/11.7 | 320 CFM |
| MC2182SC-BCD | 18,000/17,600 | 230/208 | 7.3/8.0 |
1618/1600 | 250-15A | 11.0/11.0 | 400 CFM |
| MC2242SC-BCD | 25,000/24,400 | 230/208 | 11.5/12.6 | 2536/2515 | 250-20A | 9.7/9.7 | 560 CFM |
| MC2282SC-BCD | 28,000/27,700 | 230/208 | 13.0/14.2 | 2947/2916 | 250-20A | 9.5/9.5 | 600 CFM |
| MC2362SC-BCD | 36,000/35,700 | 230/208 | 18.0/19.6 | 3913/3880 | 250-30A | 9.2/9.2 | 725 CFM |
| PROFORMANCE FOR COOLING | EVAPORATOR AIR TEMP. F. | OPERATING PRESSURES | R-22 REFRIG. CHARGE IN OUNCES | |||
| DISCHARGE AIR | TEMP DROP F. | SUCTION | DISCHARGE | |||
| MC2081SC-BCD | 56.0 | 24 | 85.0 | 252 | 23.0 | |
| MC2101SC-BCD | 57.0 | 23 | 82.0 | 266 | 26.0 | |
| MC2121SC-BCD | 53.0 | 27 | 82.0 | 266 | 32.0 | |
| MC2122SC-BCD | 57.0 | 24 | 83.0 | 258 | 28.0 | |
| MC2182SC-BCD | 53.0 | 28 | 82.0 | 255 | 44.0 | |
| MC2242SC-BCD | 50.0 | 30 | 75.0 | 255 | 53.0 | |
| MC2282SC-BCD | 53.0 | 28 | 73.0 | 259 | 50.1 | |
| MC2362SC-BCD | 49.0 | 31 | 70.0 | 287 | 57.6 | |
INSTALLATION INFORMATION
| MODEL | HEIGHT | WIDTH | DEPTH | MINIMUM ROOMSIDE EXTENSION | MINIMUM OUTSIDE EXTENSION | THRU-WALL FINISHED HOLE |
| MC2081SC-BCD | 15 15/16" | 25 15/16" | 27 3/8" | 6 1/2" | 17" | 16 1/4"h - 26 1/4" w |
| MC2101SC-BCD | 15 15/16" | 25 15/16" | 27 3/8" | 6 1/2" | 17" | 16 1/4"h - 26 1/4" w |
| MC2121SC-BCD | 15 15/16" | 25 15/16" | 27 3/8" | 6 1/2" | 17" | 16 1/4"h - 26 1/4" w |
| MC2122SC-BCD | 15 15/16" | 25 15/16" | 27 3/8" | 6 1/2" | 17" | 16 1/4"h - 26 1/4" w |
| MC2182SC-BCD | 17 15/16" | 25 15/16" | 27 3/8" | 6 1/2" | 17" | 18 1/4"h - 26 1/4" w |
| MC2242SC-BCD | 17 15/16" | 25 15/16" | 27 3/8" | 6 1/2" | 17" | 18 1/4"h - 26 1/4" w |
| MC2282SC-BCD | 20 3/16" | 28" | 33 5/8" | 6 1/2" | 19" | 20 1/2"h - 28 1/4" w |
| MC2362SC-BCD | 20 3/16" | 28" | 33 5/8" | 6 1/2" | 19" | 20 1/2"h - 28 1/4" w |
| MODEL | WEIGHT (LBS) | |
| NET | SHIP | |
| MC2081SC-BCD | 113 | 123 |
| MC2101SC-BCD | 120 | 130 |
| MC2121SC-BCD | 119 | 132 |
| MC2122SC-BCD | 119 | 133 |
| MC2182SC-BCD | 143 | 155 |
| MC2242SC-BCD | 197 | 217 |
| MC2282SC-BCD | 206 | 226 |
| MC2362SC-BCD | 221 | 241 |